TMOV14RP300E Radial leaded, P=7.5 mm – Littelfuse

Mov / varistor with varistor voltage 470V, clamping voltage 775V, and DC working voltage 385V.

Add to RFQ
SKU: TMOV14RP300E Category: Tag: Brand:
Questions about TMOV14RP300E Radial leaded, P=7.5 mm – Littelfuse ?

Key Selection Information

Selection Parameter Confirmed Information
Manufacturer Littelfuse
Exact MPN TMOV14RP300E
Product Category Varistors, MOVs
Package Radial leaded, P=7.5 mm
Packing 500 pcs/box
Varistor Voltage 470V
Clamping Voltage 775V
DC Working Voltage 385V
AC Working Voltage 300V

Product Overview

Littelfuse TMOV thermally protected radial-leaded MOV; integrated thermal element disconnects the MOV under abnormal overheating conditions. The exact MPN appears in Littelfuse application material, while the retrieved product page confirms the TMOV family function.

Integrated thermal protection addresses MOV overheating under abnormal limited-current overvoltage; it does not replace upstream overcurrent protection or appropriate enclosure/fire design.

Littelfuse TMOV14RP300E product view

Technical Specifications

Parameter Verified Information
Manufacturer Littelfuse
Exact MPN TMOV14RP300E
Functional Category Varistors, MOVs
Package Radial leaded, P=7.5 mm
Packing 500 pcs/box
Source Catalog ID C1527424
Varistor Voltage 470V
Clamping Voltage 775V
DC Working Voltage 385V
AC Working Voltage 300V

Selection Notes

MCOV; thermal protection; surge current/energy; clamp voltage; two-lead versus monitored three-lead construction.

Keep continuous operating voltage below the applicable rating and check varistor/clamping levels against both the protected node and expected surge.

Manufacturer Decision-Relevant Notes

VM(AC) 300 V RMS; surge energy 125 J; ITM 6,000 A for one 8/20-µs pulse and 4,500 A for two pulses; VN(DC) 423–517 V at 1 mA; VC 775 V; typical capacitance 400 pF; operating temperature -55 to +85 °C.

Design Considerations

  • Verify 300-V MCOV is suitable for the actual AC line and temporary overvoltages; compare 775-V clamp with insulation and protected electronics; coordinate surge energy/current with the expected standard waveform and repetitions; verify thermal-disconnect interrupt behavior and fuse coordination; confirm lead spacing and creepage for the intended mains category.

Application Fit

SPD products, UPS, AC panel protection, AC-line power supplies, surge strips, inverters, AC meters, AC/DC supplies and GFCI equipment.

Exact Variant and Procurement Notes

14 = 14-mm disc; R = round ceramic shape; P = series designator; 300 = 300-V AC class; E = two-lead TMOV without indicator lead.

Manufacturer Resources

Quality & Verification Support

Third-party inspection or testing can be arranged according to customer requirements. Testing fees are borne by the buyer. Additional verification requirements can be discussed before shipment. Physical product, label, packaging, and Date Code photos may be provided where appropriate.

Request a Quote

For TMOV14RP300E quotation, provide the exact MPN, required quantity, destination, target Date Code if applicable, and any inspection or testing requirements.

Package

Radial leaded, P=7.5 mm